Place of Origin: | China |
Brand Name: | Haodi |
Certification: | ISO |
Minimum Order Quantity: | Negotiation |
---|---|
Price: | Negotiation |
Packaging Details: | According to customer’s requirment |
Delivery Time: | 7-15days |
Payment Terms: | L/C,T/T,Paypal |
Supply Ability: | 20000 Tons/week |
Highlight: | air conditioning refrigeration cycle |
---|
R407c home, commercial air conditioning refrigerants products with 4.63 MPa
Specifications:
Physical properties |
||
Molecular formula |
|
|
Mmolecular weight |
86.20 |
|
Boiling point 101.3KPa(℃) |
-43.80 |
|
Freezing point 101.3KPa (℃) |
— |
|
Density 30℃(kg/m3) |
1129.30 |
|
Critical temperature (℃) |
87.30 |
|
Critical pressure (MPa) |
4.63 |
|
ODP |
0.00 |
|
GWP |
1700.00 |
|
Quality index |
|
Purity |
≧99.8% |
Water content |
≦0.001% |
Acidity |
≦0.00001% |
Evaporation residue |
≦0.01% |
Chloride content |
≦0.0001% |
Appearance |
Colorless and clear |
Odor |
Odorless |
Retrofit:R-407C can be used to retrofit existing R-22 systems in positive displacement, direct expansion refrigeration, and air conditioning equipment. R-407C should not be used in centrifugal chillers or other equipment that uses a flooded evaporator due, to its high temperature glide.
Retrofit Procedure
1. Establish baseline performance. Note the oil type in use and any system operating data (if system is operating properly). Check for existing leaks and identify any needed repairs.
2. Recover the existing refrigerant charge (DO NOT vent to atmosphere). Weigh the amount of refrigerant removed.
3. Drain existing oil from the compressor sump, suction line accumulators, etc. Record the amount of oil removed. Add an equivalent amount of OEM recommended POE oil.
4. Recharge the system with the recovered R-22 charge and run the system (at least 1 hour) to circulate the new lubricant.
5. Recover the R-22 charge again and check the residual oil content of the lubricant. The amount of the original lubricant in the POE must be less than 5%.
6. Repeat steps 3 – 5, as needed, until the required oil purity level is reached. Once the oil flushes are completed, standard maintenance should be conducted (i.e. filter-drier change, leak repairs).
7. Evacuate the system (less than 500 microns) and ensure it maintains a vacuum. If vacuum is lost, it may indicate that leaks are present in the system.
8. Charge system with R-407C refrigerant. Remove refrigerant as liquid only from cylinder. The initial charge weight should be approximately 90% of the standard charge for R-22, charging up to 95% if necessary.
9. Adjust TXV set point and/or refrigerant charge to achieve the desired superheat. Low side pressure control settings may also need to be adjusted.
10. Monitor oil level in the compressor. If necessary, adjust oil amount to attain normal operating level(mid-sight glass).
11. Label system clearly, indicating the type and amounts of system refrigerant and oil.
Applications:
Applications include residential and commercial air conditioning systems, non-flooded evaporator chillers, and some commercial refrigeration systems. Since R-407C has similar properties to R-22, it is possible (with modifications) to use it in the same equipment designed for R-22 today.
Competitive Advantage:
1.R407c of all specifications
2.OEM is accepted
3.Purity 99.8%
4.Certifications of
SGS/ROSH/PONY/ISO9001/ISO14001/ISO169
Contact Person: Ms. Hu
Tel: 1393380568
Fax: 86-755-3987544
Industrial Grade Mixed refrigerant Retrofited refrigerant for R22
Mixed refrigerant / Retrofited refrigerant for R22 and R502
Mixed Refrigerant R404A (HFC-404A) Recyclable cylinder 400L / 800L / 926L
Economical R134 replacement (HCFC) r22 refrigerant cylinder / chlorodifluoromethane r22
R22 Refillable cylinder Odorless 1000L CHCLF2 R22 Refrigerant Replacement
R22 Replacement Chlorodifluoromethane (HCFC-22) home air conditioner refrigerant gas
R134a Pure gas cooling agent R134a refrigerant 30 lb Air Conditioning and Heat Pumps
Car automotive air conditioning r 134a refrigerant 30 lb, High Purity 99.90%
HFC R134a Auto air conditioning CH2FCF3 R134a Refrigerant 30lbs for commercial, industrial